How to read the chart
Find the band your room falls in. The BTU column is the ENERGY STAR value for an 8-foot ceiling with average sun. The last two columns add 10% for a very sunny room, then another 10% for a hot climate. The mini split column shows the standard size that covers the normal-conditions load.
Adjustments ENERGY STAR recommends
- Heavily shaded room: reduce capacity by 10%.
- Very sunny room: increase capacity by 10%.
- More than two people regularly in the room: add 600 BTU per extra person.
- Unit used in a kitchen: add 4,000 BTU.
The chart assumes an 8-foot ceiling. Our BTU calculator also scales for taller ceilings, climate and insulation.
Window AC and central air
Window and portable units come in steps such as 5,000, 6,000, 8,000, 10,000, 12,000, 14,000, 18,000 and 24,000 BTU. Pick the step at or just above the chart value. Central systems come in half-ton steps from 1.5 tons (18,000 BTU) and should be sized for the whole house with a Manual J calculation rather than by adding up rooms.
Source: ENERGY STAR, room air conditioner sizing guidance.